Note*: The neutral pole (N pole) of the four-level product is divided into four types of 
A-type N-pole, no overcurrent tripping element is installed, and the N-pole is always on, not combined with other three-level; 
B-type N-pole No overcurrent trip element is installed, and the N pole is combined with other three levels (N pole is closed first and then opened); 
C-type N pole is installed with overcurrent trip element, and the N pole is combined with other three levels (N The pole is closed first and then opened); 
D-type N pole is installed with an overcurrent trip element, and the N pole is always on, and does not open and close together with other three levels;
	1. The upper limit of ambient air temperature is +40¡æ, the lower limit is -5¡æ, and the average value of 24h does not exceed +35¡æ. 
2. Altitude: The altitude of the installation site does not exceed 2000m. 
3. Relative humidity: the relative humidity of the atmosphere does not exceed 50% when the ambient air temperature is +40¡æ, and it can have a higher relative humidity at a lower temperature; the monthly average maximum relative humidity of the wettest month is 90%, and the The monthly average minimum temperature of the month is +25¡ãC, taking into account the condensation on the surface of the product due to temperature changes. 
4. Pollution degree: Pollution degree is 3